CV Transmitter Toxic/Oxygen




Input Voltage 12-30v DC - 24v nominal
Output Standard Analogue 4- 20 ma (250 ohms max) - source
Option 1 - 5v output – solder G
Alarm Relay Board Options 3 wire system only (2 wire if the 4~20mA signal is not used)

(safe area board only)

Signal relay contacts S.P.C.O. rated 1A/24v (Logic and fire panel signal only)
Mains relay S.P.C.O. 5A/230v AC
Trip Indicator LED – trip point selectable 10% to full scale
Fire Alarm panel signalling – cut F
Logic output - JP3 position L and end of line link JP4
Full Board Options
(safe area board only)
On board sounder
Auxiliary output DC volts - standard - as input volts 24v
(selection by fixed voltage regulator U5 - 5,12, 15 volts)
DPM - gas readout display - (zero and span potentiometers used only for DPM setting)





INSTALLATION
Siting of the equipment should be chosen with regard to the following points.
a. Away from sources of heat with room for adequate air circulation.
b. Within easy reach for operating and maintenance personnel.
c. Connecting cables to be electrically shielded ie: M.I.C.C., steel wire armoured, screened cable or steel conduit.
Note: Sensor cables should not be run in the same ducting as power cables.

CALIBRATION
1. Connect a digital voltmeter (miIIivolt range) to the + and – test terminals (2 wire system) or X and Y test terminals (3 wire system)
For 3 wire systems the CV is preset in the current source
mode.
2. In clean air check that the DVM reads 4mV, if not adjust the 4mA potentiometer on the CV transmitter board.
3. Apply test gas and wait until a maximum DVM reading is
obtained, if necessary adjust the 20mA potentiometer for the
required mV reading for the calibration gas used (see range/reading on test certificate or printed on the CV circuit
board).
4. For oxygen level monitoring remove the sensor terminal
connector from the PCB J4 and adjust the 4mA potentiometer
for 4mA (4mv).
Reconnect the cell and allow reading to stabilise adjust the DVM reading for 17.3mA (20.8% Vol. ambient oxygen) using the 20mA potentiometer.
Where a Digital panel meter is fitted readings should be taken directly from the readout and if required adjusted using the 4-20mA potentiometers.

ADDITIONAL RELAY BOARD ALARMTRIP POINT ADJUSTMENT
This level will normally be set at 20% of the range reading i.e. 7.2mA.
1. Connect the DVM as above, using the 4mA potentiometer adjust for the required trip level.
2. Adjust the alarm level potentiometer until the alarm LED just comes on.
3. Using the 4mA potentiometer re-adjust the DVM to 4mV.
The above adjustment may be carried out in house by connecting the CV transmitter directly to a DC power supply.
Should a full board be required to operate on a 2 wire loop then the relay must be disabled - remove JP2

Gas Type Programming – Works/preset.
CO. H2S, SO2. H2 remove R4, R6, R15, R28, R29, R10
HCN remove R4, R6, R8, R15, R28, R29, R10
NO2, CL2 O3, remove R4, R7, R11, R28, R29, R10
NO, HCL, C2H4O Remove R3, R4, R6, R12, R15, R28, R29, R10


   
GDS Technologies Ltd
Fusion Point, Ash Lane, Garforth,
Leeds UK LS25 2GA
Tel +44 (0)113 286 0166
Fax +44 (0)113 287 8178
Email sales@gds-technologies.co.uk
www.gds-technologies.co.uk
GDS Technologies

This document is not contractual and the equipment specification may be modified at any time without prior notice.