INSTALLATION
Siting of the equipment should be chosen
with regard to the following points.
a. Away from sources of heat with room
for adequate air circulation.
b. Within easy reach for operating and
maintenance personnel.
c. Connecting cables to be electrically
shielded ie: M.I.C.C., steel wire armoured,
screened cable or steel conduit.
Note: Sensor cables should not be run
in the same ducting as power cables.
SET UP
1. Having powered up allow 5 minutes for
the sensor to stabilise.
2. SAFE AREA SENSOR BOARD - the sensor
current/voltage should be set by connecting
a voltmeter (mV meter reading = mA sensor
current) CAUTION - DO NOT EXCEED 360mV
(mA).
EExd SENSOR BOARD - measuring across sensor
terminals W and P adjust the sensor voltage
potentiometer for required voltage.
3. Zero the card in clean air by adjustment
of the potentiometer marked zero until
the GREEN ON/Z LED just turns from GREEN/RED
to GREEN. (At this point the output will
= 4ma). If you require to check this,
connect a digital meter (mV range) to
the test pins marked TP1 and TP2, if adjustment
is required adjust the 4ma potentiometer
(4mV = 4mA). |
CALIBRATION
With the digital meter connected to the
test pins TP1 and TP2 and a reading of
(4mV clean air) apply test gas and wait
until a maximum reading is obtained, if
necessary adjust 20mA potentiometer for
the required mV reading for the calibration
gas being used.
Where 4 to 20mA span = 0 - 100% L.E.L.
(Lower explosive level) and the sensor
is to be calibrated for Methane which
has an L.E.L. of 5% vol, when using 1%
Methane in air test gas (20% L.E.L.) a
reading of 7.2mc (7.2mA) would be required.
Where a digital panel meter is fitted
readings should be taken directly from
the readout and if necessary adjusted
using the 4 and 20mA potentiometers.
ADDITIONAL RELAY BOARD ALARM TRIP POINT
ADJUSTMENT
This level will normally be set at 20%
of the range reading i.e. 7.2mA.
1. Connect the DVM as above, using the
zero potentiometer adjust for the required
trip level (mv).
2. Adjust the alarm level potentiometer
until the relay just changes state.
3. Using the zero potentiometer re-adjust
the DVM to 4mV.
The above adjustment may be carried out
in house by connectiong the CV transmitter
directly to a DC power supply. |
|
|
| |
|