Tel: 0113 286 0166
Fax: 0113 287 8178
 
Red Line 9000 Carbon Dioxide Sensor Infra Red Gas Sensor





Certification
CE – C509
Input voltage – 3 wire device
(polarity protected)
12 to 35V DC – 24v DC nominal
Maximum current consumption 130mA
Voltage output 1~5V, maximum current draw 5mA
Resolution 0.15% of span
Output 4~20mA (link selectable as sink or source)
Maximum loop resistance in source mode 250R
Output resolution 0.02mA
Maximum offset drift ± 20uA
Over-range output 21.3mA (typical)
Fail signal 4~20mA reduced to 3mA
Fail indicator Open collector output to 0V



Ineternal plug in sensor
(NDIR)

Processor and terminal enclosure – material

GRP
Dimensions 122mm x 122mm x 76mm
Weight 0.8Kg
Mounting Entry Two M5 (145 mm CRS) 45° from vertical
On Board Indicators: -  
Green LED System healthy
Three red LED’s System diagnostics
Cable Entry One – 20 mm 1.5 pitch



IP53 + Water Shield IP64

Operating Conditions
0 ~100% RH (non-condensing)
-10 ~ +50°C

Storage Conditions
0~100% RH (non-condensing)
-20 ~ +60°C

Accessories:-
003-040 Collector Cone + universal fitting
003-003 Universal fitting – Test Gas Applicator
Weather Cone
008-312 Flow Block
003-036 Duct Mount Probe
   
GDS Technologies Ltd
Fusion Point, Ash Lane, Garforth,
Leeds UK LS25 2GA
Tel +44 (0)113 286 0166
Fax +44 (0)113 287 8178
Email sales@gds-technologies.co.uk
www.gds-technologies.co.uk
GDS Technologies


This document is not contractual and the equipment specification may be modified at any time without prior notice.




Welcome to GDS | Fixed System Detectors | Flow Sample System Sensors
Portable Gas Detectors | Remote Detection Alarms | Gas Detection Sensors
Hazardous Area Gas Detectors
| Safe Area Gas Detectors
Gas Detection Leakage Survey | Gas Sensor Locations