Tel: 0113 286 0166
Fax: 0113 287 8178
 




Applications Car parks, boiler/plant rooms, commercial/public buildings
Sensing Principle Catalytic combustion - continuous diffusion
Operating Range 0-100%LEL
Operating Voltage 2.5v DC
Operating Current 170mA
Housing Material Nickel plated brass
options: stainless steel 316-516, plastic, customer specification
Dimensions Length 21mm Dia 20mm
Thread 20mm 1.5mm pitch
options: 25mm 1.5mm pitch, 3/4 NPT-14, customer specification
Weight 35 grams
Lead Length 120mm


Sensitivity 20mV/1% Methane
Zero Stability <± 8% FSD/year
Response Time T90 10 seconds to 1% Methane
Operating Temperature -20 to +50°C
Ingress protection IP53 + weather cone IP63
Operating Life >5 years clean environment


Supplied items F5 sensor + 1 locknuts – M20
Part No. 001-403 others available
Design Reg. No. 3023139
Classification None – EExd version pending
4~20mA Output board see data sheet C323
Junction Box Housing see data sheet C448
Alarm Panels See data sheet C376


Weather cone Part No 003-030
Test Gas Applicator  
Collector cone Part No 003-040
Test Gas Applicator  
Flow Block Part No 008-312


   
GDS Technologies Ltd
Fusion Point, Ash Lane, Garforth,
Leeds UK LS25 2GA
Tel +44 (0)113 286 0166
Fax +44 (0)113 287 8178
Email sales@gds-technologies.co.uk
www.gds-technologies.co.uk
GDS Technologies

This document is not contractual and the equipment specification may be modified at any time without prior notice.





Welcome to GDS | Fixed System Detectors | Flow Sample System Sensors
Portable Gas Detectors | Remote Detection Alarms | Gas Detection Sensors
Hazardous Area Gas Detectors
| Safe Area Gas Detectors
Gas Detection Leakage Survey | Gas Sensor Locations