Tel: 0113 286 0166
Fax: 0113 287 8178
 
GDS404 1-4 Channel Gas Alarm





Outputs

4 user selectable. S.P.C.O. Zone/voting – time ON/OFF delay
1 common low alarm D.P.C.O
1 common high alarm D.P.C.O
1 common overange S.P.C.O
1 common fault alarm S.P.C.O
NE/ND
All contacts rated @ 5A-230v AC
General alarm relay - resetable S.P.C.O. - for sounders etc.
Optional 64 relays - programmable
2 channel 4~20mA - assignable to any group of sensors
RS232 data log - event log
Modbus - RS485 x2
24v DC output fused at 1Amp
Audible Alarm Alarm/Fault - permanent mute option
Power Consumption 230/115v AC or 24v DC
Control unit 7.5w quiescent 17w full alarm
Sensor - 2.5w
Internal power supply
- 20 sensors max
- 20+ sensors GDS 10PS Power Pack
Sensor Cable - Addressable Direct
Main network - 4 core (2 power - 2 comms)
2/3 core

1.5mm2 screened
max length 1km

Miscellaneous Enclosure cable entry - bottom, rear, top
Remote reset/mute
Front panel button – key lock
Repeater panel
16 way 4~20mA catalytic converter panel
LED indication – Con fail, Modbus fail, MPU fail
Password protection - user mode/engineers mode
LCD and LED dimming
Environmental Control unit - IP52
Operating temperature -10 + 50°C
Dimensions 315W x 265H x 95D - Combi panel
315W x 265H x 95D - GDS 10PS power supply
Weight 4.95Kg





 

GDS Technologies Ltd
Fusion Point, Ash Lane, Garforth,
Leeds UK LS25 2GA
Tel +44 (0)113 286 0166
Fax +44 (0)113 287 8178
Email sales@gds-technologies.co.uk
www.gds-technologies.co.uk
GDS Technologies


This document is not contractual and the equipment specification may be modified at any time without prior notice.




Welcome to GDS | Fixed System Detectors | Flow Sample System Sensors
Portable Gas Detectors | Remote Detection Alarms | Gas Detection Sensors
Hazardous Area Gas Detectors
| Safe Area Gas Detectors
Gas Detection Leakage Survey | Gas Sensor Locations