GDS100 Single Point Gas Alarm





Power Supply
230/115v AC 50/60 Hz or 24vDC
The two voltages may be utilised simultaneously - standby battery
Power Consumption 4 watts - full alarm
Outputs Low, High and Fault alarm relays - SPCO normally de-engerised - energised option
Lo gas alarm relay SPCO normally energised - de-energised option
latched or unlatched
Fault relay SPCO normally de-energised - energised option
All contacts rated 5A - 230v AC
4-20mA/1-5v
Alarm Settings Digital setting (fully adjustable between zero and full scale)
Sensor Inputs Bridge type 3 wire detector mv (Catalytic)
4-20mA (electrochemical/infrared
Sensor Cable 3 core 1.5mm2 screened 1.5km
Miscellaneous Alarm relay inhibit during calibration
Sounder Inhibit
System function test switch
Dimensions L200mm H 120mm D 58mm
Weight 0.8kg
Protection IP65
Operating temperature - 10 to +50°C
Storage temperature - 10 to 65°C
Field Terminals - screw type 2.5mm
Cable entry - top, bottom, sides, rear
24vDC 200mA output



Gas Sensors





 
GDS Technologies Ltd
Fusion Point, Ash Lane, Garforth,
Leeds UK LS25 2GA
Tel +44 (0)113 286 0166
Fax +44 (0)113 287 8178
Email sales@gds-technologies.co.uk
www.gds-technologies.co.uk
GDS Technologies


This document is not contractual and the equipment specification may be modified at any time without prior notice.




Welcome to GDS | Fixed System Detectors | Flow Sample System Sensors
Portable Gas Detectors | Remote Detection Alarms | Gas Detection Sensors
Hazardous Area Gas Detectors
| Safe Area Gas Detectors
Gas Detection Leakage Survey | Gas Sensor Locations