GDS - Gas Detection Systems and Equipment Technologies Ltd
Home GDS Products Services About Us Technical Data Downloads News/Products Contact Us

Fixed Systems
Combi
Gas Net
GDS 404
GDS 2010
GDS 100
GDS 202
GDS 10
Back To Fixed Systems


Auxiliary Equipment

 

 
 

GDS100
C292
(Single Point Gas Sensor)


Search


 



Power Supply
230/115v AC 50/60 Hz or 24vDC
The two voltages may be utilised simultaneously - standby battery
Power Consumption 4 watts - full alarm
Outputs Low, High and Fault alarm relays - SPCO normally de-engerised - energised option
Lo gas alarm relay SPCO normally energised - de-energised option
latched or unlatched
Fault relay SPCO normally de-energised - energised option
All contacts rated 5A - 230v AC
4-20mA/1-5v
Output 24vDC @ 100mA max - auxiliary equipment (non inductive)
Alarm Settings Digital setting (fully adjustable between zero and full scale)
Delay to alarm options - 10/30 seconds, 10 minutes
Sensor Inputs Bridge type 3 wire detector mv (Catalytic)
4-20mA (electrochemical/infrared
Sensor Cable 3 core 1.5mm2 screened 1.5km
Miscellaneous
GDS100 Operating temperature -10 to +50°C
Storage temperature -10 to 65°C
Alarm relay inhibit during calibration
Sounder Inhibit
System function test switch
Dimensions L200mm H 120mm D 58mm
Weight 0.8kg
Protection IP65
Field Terminals - screw type 2.5mm
Cable entry - top, bottom, sides, rear





Gas Sensors





 

GDS Technologies Ltd
Fusion Point, Ash Lane, Garforth,
Leeds UK LS25 2GA
Tel +44 (0)113 286 0166
Fax +44 (0)113 287 8178
Email sales@gds-technologies.co.uk
www.gds-technologies.co.uk
GDS Technologies


This document is not contractual and the equipment specification may be modified at any time without prior notice.



Copyright © 2009 GDS Technologies Ltd - Gas Detection Systems and Equipment.