Tel: 0113 286 0166
Fax: 0113 287 8178
 
GDS202 Flammable/Toxic/Oxygen/Refrigerant Gas Alarm



Toxic/Flammable/Refrigerant sensor combination
Standard Unit 1 - 10 Sensors
Four zone indicators
Single cable for multiple sensors
Individual Sensors with audible and visual warning alarms
Sensors pre-set and tested
Self diagnostic
Pre and full alarm indication
Two alarm relays
Wall or panel mount
Designed for ease of installation
System easily extended
Off the shelf system



The GDS 202 gas leak detection system features a main control unit connected to remote sensors via a single 3 core cable. The control unit is of an advanced design using the latest technology and provides a high integrity system whilst enabling a significant cost saving over convential gas alarm systems.

Standard sensors for use in commercial and light industrial applications such as laboratories, workshops, boiler plant rooms etc are available for monitoring carbon monoxide, flammable or refrigerant gases. Each sensor incorporates a status LED and alarm sounder. Sensor types may be mixed and up to 10 in number for the standard control unit, or up to 20 when used with an optional auxiliary power pack. Alternatively sensors may be used separately without a control unit providing they are powered by a 12 or 24volt DC supply.

Senors are also available for a wide range of special gases in standard or certified flameproof enclosures for hazardous area use in heavy industrial or petrochemical installations.



On power up, the green power indicator will flash for 3 minutes indicating that the sensors are stabililsing, during this timed period all alarm functions are held in the off condition.

After the stabilisation period, any sensor detecting gas will provide a local visual (red LED) and audible alarm, at the same time transmitting a signal to the control unit where a pre alarm is indicated by an intermittent audible alarm, with the red zone alarm LED flashing and the pre alarm relay changing state. Should the gas surrounding the sensor clear within 45 seconds the system will return to the normal operating condition. However, if the gas remains for longer than 45 seconds, full alarm condition will occur and be indicated by the red alarm LED and sounder going constant as well as the full alarm relay activating.

The audible alarm may be silenced at any time but full alarm indication will be latched until the gas has cleared after which the system may be reset by pressing the reset pad.



Control Unit - A two-part screw together polycarbonate enclosure houses the power supply alarm indicators, control functions, and alarm relays. The enclosure may be wall or panel mounted having cable entry from the rear, bottom, top or sides.

Standard Sensors - Two-part push together plastic enclosure that may be surface mounted using two fixing points or attached directly to a standard conduit box, cable entry is from the rear.

Hazardous area and special gas sensor - see data sheet C389





Welcome to GDS | Fixed System Detectors | Flow Sample System Sensors
Portable Gas Detectors | Remote Detection Alarms | Gas Detection Sensors
Hazardous Area Gas Detectors
| Safe Area Gas Detectors