GDS202
C484
(Flammable/Toxic/Oxygen/CO2/Refrigerant Gas Alarm)


Search


 




Power Supply
115/230vAC or 24vDC ±15%
The two voltages may be used at the same time (standby battery)
Power Output 24vDC-200mA max. - auxiliary equipment
Frequency 50/60 Hz
Consumption 3 watts
Detector Head l to 10 Toxic and/or flammable sensors
Indicators Power - (Green LED)
Pre alarm - (Flashing red alarm LED and intermittent sounder) non latch
Full alarm - (Constant red alarm LED and sounder) - latching (option non latch)
Fault - (Amber LED and sounder) Fault monitoring - sensor/sensor cable/control unit - non latching
Sensor Cable 3 core 1 mm2
Cable length - 200m max
Alarm Relays Pre alarm S.P.C.O (R1)
Full alarm D.P.C.O (R2)
Fault alarm S.P.C.O (R3)
Relays are de energised in non-alarm state (option-energised)
All contacts rated -5A@230v AC.
Relay Inhibit Front Panel Access
Protection IP65
Weight 920gms
Operation -5 to +45°C
Storage +10 to +60°C
Dimensions L 200mm x H 120 mm x D 58 mm
Miscellaneous Remote test, remote inhibit, remote sounder, premanent mute


Power Supply 12 to 30v DC
Consumption 1.2W
Indicators Power (Green LED)
Gas Alarm (Green LED to red and sounder) - non latching
Alarm Threshold Preset (adjustable)
Ambient Temp Operation: -5 to 45°C Storage: +10 to +60°C
Protection IP42
Weight 115gms
Dimensions L 83 x H 83 x D36mm





The system may be electrically tested by pressing the test pad located on the control unit for 15 seconds, after which the pre-alarm state will be initiated with the exception of the relay, by maintaining pressure on the test pad for a further 15 seconds a full alarm condition will result including the operation of both relays.
Each sensor has an individual test switch which when pressed simulates gas present and turns the green LEDto red and switches the sounder on.

To ensure that the system responds correctly to the presence of gas, each sensor should be exposed to test gas. It is advisable to carry out this test at least every six months. -

During test periods alarm relays may be inhibited by pressing the reset pad for four seconds after which the fault indicator will illuminate and maintain all relays in the normal non-alarm state. F F




Control Unit order code 200-011
Optional Auxiliary Power Supply order code 200-005
Flammable Sensor order code 200-010
Refrigerant Gas Sensor order code 200-030
Carbon Monoxide Sensor order code 200-020
Hydrogen Sulphide order code 200-040
Other gas type sensors available    

CE936
 

GDS Technologies Ltd
Fusion Point, Ash Lane, Garforth,
Leeds UK LS25 2GA
Tel +44 (0)113 286 0166
Fax +44 (0)113 287 8178
Email sales@gds-technologies.co.uk
www.gds-technologies.co.uk
GDS Technologies


This document is not contractual and the equipment specification may be modified at any time without prior notice.



Copyright © 2009 GDS Technologies Ltd - Gas Detection Systems and Equipment.