GDS202 Flammable/Toxic/Oxygen/Refrigerant Gas Alarm






Power Supply
115/230vAC or 24vDC ±15%
The two voltages may be used at the same time (standby battery)
Power Output 24vDC-200mA max. - auxiliary equipment
Frequency 50/60 Hz
Consumption 3 watts
Detector Head Standard 1 to 10 (Auxillary power supply 1 to 20) Toxic and/or flammable sensors)
Indicators Power - (Green LED)
Pre alarm - (Flashing red alarm LED and intermittent sounder) non latch
Full alarm - (Constant red alarm LED and sounder) - latching (option non latch)
Fault - (Amber LED and sounder) Fault monitoring - sensor/sensor cable/control unit - non latching
Sensor Cable 3 core 1 mm2
Cable length - 200m max
Alarm Relays Pre alarm S.P.C.O (R1)
Full alarm D.P.C.O (R2)
Fault alarm S.P.C.O (R3)
Relays are de energised in non-alarm state (option-energised)
All contacts rated -5A@230v AC.
Relay Inhibit Front Panel Access
Protection IP65
Weight 920gms
Operation -5 to +45°C
Storage +10 to +60°C
Dimensions L 200mm x H 120 mm x D 58 mm
Miscellaneous Remote test, remote inhibit, remote sounder, premanent mute



Power Supply 12 to 30v DC
Consumption 1.2W
Indicators Power (Green LED)
Gas Alarm (Green LED to red and sounder) - non latching
F200 Flammable Gas Alarm Threshold F200 1% CH4 Adjustable
T200 Carbon Monoxide Alarm Threshold T200 50ppm Adjustable
R200 Refrigent Gas Alarm Threshold R200 Adjustable
Ambient Temp Opeation -5 to 45°C
Storage +10 to +60°C
Protection IP42
Weight 115gms
Dimensions L 83 x H 83 x D36mm



The system may be electrically tested by pressing the test pad located on the control unit for 15 seconds, after which the pre-alarm state will be initiated (with the exception of relay). By maintaining pressure on the test pad for a further 15 seconds a full alarm condition will result (including the operation of both relays).
Each sensor has an individual test switch which when pressed simulates gas present and turns the green LED to red and switches th sounder on.
To ensure that the system responds correctly to the presence of gas, each sensor should be exposed to test gas. It is advisable to carry out this test at least every six months.
During test periods alarm relays may be inhibited by pressing the reset pad for four seconds after which the fault indicator will illuminate and maintain all relays in the normal non-alarm state.



Control Unit

order code 200-011

Optional Auxillary Power Supply

order code 200-002

Flammable Sensor

order code 200-010

Carbon Monoxide Sensor

order code 200-020

Refrigerant Gas Sensor

order code 200-030
Other gas type sensors available    

 
GDS Technologies Ltd
Fusion Point, Ash Lane, Garforth,
Leeds UK LS25 2GA
Tel +44 (0)113 286 0166
Fax +44 (0)113 287 8178
Email sales@gds-technologies.co.uk
www.gds-technologies.co.uk
GDS Technologies


This document is not contractual and the equipment specification may be modified at any time without prior notice.