Sensor Points
|
Unlimited 10 per 19" 3U section |
| Measurements
|
Combustible gas L.E.L. % Vol
Toxic gas P.P.M. % Vol
Oxygen - % Vol
depletion/enrichment
Refrigerant ppm |
| Power
Supply |
230/115v AC 50/60 Hz |
| Consumption |
350 watts |
| Indicators |
Digital Display 3 1/2 digit
gas readout
Power, twin green L.E.D.s
Low alarm, red L.E.D. per channel
Latched or unlatched option
High alarm, red L.E.D. per channel
Latched or unlatched option
System fault, twin amber L.E.D.s
Flow fail, twin amber L.E.D.s
Channel selection, green L.E.D.s
Purge, twin green L.E.D.s |
|
User Interface |
Panel mounted push buttons
(two), hold, step, mute and
reset functions |
|
Alarm Settings |
Digital setting, fully adjustable between
zero and full scale |
Outputs
|
High level gas alarm relay
D.P.C.O. (global)
Low level gas alarm relay
D.P.C.O. (global)
Fault alarm relay
S.P.C.O. (global)
Flow fail alarm relay, S.P.C.O.
Mains fail relay, S.P.C.O. N/E
All contacts rated 5A 230v AC
4~20mA analogue output or 1~5v
Optional data logger |
|
|
|
Optional - 20-way relay board
1 relay per alarm level
Power output 24v DC
200mA max. Auxiliary equipment |
|
Audible Alarm |
Lo, hi and fault alarms |
| Dimensions |
1~20 way sample system
H380mm x W600mm x D370mm
1~40 way sample system
H600mm x W600mm x D370mm |
|
Weight |
1~20 way sample system 33kg
1~40 way sample system 42kg |
|
Finish |
Epoxy coated steel |
| Ingress
Protection |
IP55 |
| Fixing
Details |
Wall mount 4 x M8 |
| Sample
Line |
Material: Nylon, PTFE,
Stainless Steel, Copper
Size - 6mm OD, 4mm ID
Optional 8mm OD, 6mm ID
Max. length 6mm OD tube 100m
8mm OD tube, 200m
Specials, 300m + |
| Tubing
Entry |
1~20 way enclosure base
1~40 way
Left and right hand enclosure sides |
| Sample
Vent |
10mm |
| Line
Blockage |
Blow-back air supply
4 bar max - option |
| Operating
Temp |
0 to 40°C |
| Sample
Temp |
-5 to +50°C
high temperature versions available |
| Sample
Flow Rate |
~ 4 m/s |
| Response
Time |
15 to 60 seconds |
|