GDS - Gas Detection Systems and Equipment Technologies Ltd
Home GDS Products Services About Us Technical Data Downloads News/Products Contact Us

Flow Sample Systems
GDS 301
GDS 302
GDS 305
GDS 306
GDS 307
Undergoing Technical Updates
Back To Flow Sample Systems


Auxiliary Equipment
 
 

GDS301

(Single Line Sample Unit)

Search


 




Measurements Combustible Gas L.E.L %Vol, ppm
Toxic Gas - ppm, %Vol
Oxygen - % Vol
Power Supply 230/115vAC or 24vDC ± 15%
The two voltages may be used
simultaneously (standby batteries)
Frequency 50/60Hz
Consumption 10 watts
Alarm Settings Digital setting (fully adjustable
between zero and full scale)
Alarm delay T1 - 10 seconds, T2 - 30 seconds,
T1 + T2 - 10 minutes
Indicators Power - Green L.E.D.
Alarms - Low/High - Red L.E.D.
Flow fail - Amber L.E.D.
Fault - Amber L.E.D.
System test alarm L.E.D's flashing
Outputs Low alarm relay - S.P.C.O
High alarm relay - S.P.C.O
Fault alarm relay - S.P.C.O
Flow fail - S.P.C.O
Relays rated 5A/230vAC
ND or NE pre set normally de energised
Analogue 4-20mA/1-5v
24vDC - 100mA max
(Auxiliary equipment supply)
Audible Alarm
Low, High gas and Fault
Permanent mute option
Reset Switch Auto or Manual - pre set manual
Test Switch Used to check alarm indicators, sounder and relay action
Inhibit Isolation of alarm relays during service
Protection IP65
Environmental Ambient temperature -5 to 45°C
Storage temperature +10 to 60°C
Humidity range 0 - 90 RH
Cable Entry Rear, side, top, bottom
Sample Tube 6mm OD 4mm ID
Max. length 100m
Exhaust port 8mm OD
Miscellaneous Dimensions 315mmW 265mm H 95mm D
Weight 3.8kg
Cable entry - bottom, sides, rear

GDS 305


 

GDS Technologies Ltd
Fusion Point, Ash Lane, Garforth,
Leeds UK LS25 2GA
Tel +44 (0)113 286 0166
Fax +44 (0)113 287 8178
Email sales@gds-technologies.co.uk
www.gds-technologies.co.uk
GDS Technologies


This document is not contractual and the equipment specification may be modified at any time without prior notice.