Sensor Points
|
1-10 |
|
Measurements |
Combustible gas L.E.L. % Vol
Toxic gas P.P.M. % Vol
Oxygen - % Vol depletion/enrichment
Refrigerant ppm |
|
Power Supply |
230/115v AC 50/60 Hz |
|
Consumption |
100 watts |
|
Indicators |
Digital Display 3 1/2 digit gas readout
Power, twin green L.E.D.s
Low alarm, red L.E.D. per channel
High alarm, red L.E.D. per channel
System fault, twin amber L.E.D.s
Flow fail, twin amber L.E.D.s
Channel selection, green L.E.D.s
Purge, twin green L.E.D.s |
|
User Interface |
Panel mounted push buttons (two), hold,
step, mute and reset functions |
|
Alarm Settings |
Digital setting, fully adjustable between
zero and full scale
|
Outputs
|
High level gas alarm relay D.P.C.O. - sequential
operation
Low level gas alarm relay D.P.C.O. - sequential
operation
Global alarm relay maintained - selectable
low or high alarm D.P.C.O.
Fault alarm relay S.P.C.O.
Flow fail alarm relay, S.P.C.O.
Mains fail relay, S.P.C.O. N/E
All contacts rated 5A 230v AC
4~20mA analogue output or 1~5v
Optional data logger |
|
|
|
Optional - 20-way relay board 1 relay per
alarm level
Power output 24v DC 200mA max. Auxiliary
equipment |
|
Audible Alarm |
Lo, hi and fault alarms |
|
Dimensions |
H400mm x W400mm x D200mm |
|
Weight |
14.5kg |
|
Finish |
Epoxy coated steel |
|
Ingress Protection |
IP55 |
|
Fixing Details |
Wall mount 4 x M8 |
| Sample
LIne |
Material: Nylon, PTFE,
Stainless Steel, Copper
Size - 6mm OD, 4mm ID
Optional 8mm OD, 6mm ID
Max. length 6mm OD tube
100m 8mm OD tube, 200m
Specials, 300m + |
|
Sample Vent |
10mm |
| Line
Blockage |
Blow-back air supply
4 bar max - option |
| Operating
Temp |
0 to 40°C |
| Sample
Temp |
-5 to +50°C
high temperature versions available |
| Sample
Flow Rate |
~ 4 m/s |
| Response
Time |
15 to 60 seconds |
| Tubing
Entry |
Enclosure base |
|