Tel: 0113 286 0166
Fax: 0113 287 8178
 
GDS404 1-4 Channel Gas Alarm





Fault Alarm Relay - Common S.P.C.O
Normally energised or de-energised
Channel Relays - 1 per channel high or low selectable S.P.C.O
Normally energised or de-energised, latched or unlatched
General Alarm Relay - resetable S.P.C.O
All contracts rated 5A-230vAC
Analogue 4~20mA output per channel
Output 24vDC @ 100mA max
Audible Alarm Permanent mute option
Lo, Hi, Fault alarms
Alarm Settings Digital Setting (fully adjustable between zero and fullscale)
Sensor inputs Bridge type 3 wire mV input
4~20mA (electrochemical/infrared)
Sensor cable 3 core 1.5mm2 screened <1.5km
Miscellaneous EMC approvals EN50270 Marine EN60945
Enclosure - cable entry - bottom/rear
Protection IP52 - option IP65
Dimensions W310 x H265 x D75mm
Weight 3.6kg
Operating temperature - 10 to +50°C
Optional fron cover lock
Optional backup battery
Field terminals - 2.5mm quick release
Relative Humidity 0 - 90%
System/lamp test
Remote Accept/Reset
Alarm isolate during service






Repeated for each channel 14-21

 