COMBI 64 Panel Mount

COMBI 64 Panel Mount

Combi 64 Addressable has been designed to operate in the full range of environments from commercial premises through to heavy industrial applications which may require hazardous area sensing. Typical monitor locations are – public buildings, car parks, tunnels, breweries, boiler plant rooms, water treatment works, H&V control, manufacturing, process plants, horticulture, hotels, offices.



Combi Controller Configuration

Specifications

Sensor points
1~64 addressable  – CANbus

Measurements
Combustible gas – L.E.L., % vol
Toxic gas – ppm, % vol
Oxygen –  % vol – depletion/enrichment
Refrigerant – ppm
Any 4~20mA transmitter

Indicators
Dot matrix LCD 4 line 40 character - indicating sensor location, gas type (rising or falling alarms), alarm status, system fault, sensor line fault, sensor fault, inhibit,  real time clock, event memory
Red LED – global alarm
Amber LED – global fault  
Amber LED – inhibit

Outputs  
Separate 8 way relay module
8 user selectable zone/voting – with NE/ND option  and delay to de-energise
Relay contacts – 2 D.P.C.O / 6 S.P.C.O.  
rated @ 5A-230v AC

Factory set
1 common low alarm D.P.C.O or group 1  
1 common high alarm D.P.C.O or group 2  
1 common overange S.P.C.O or group 3  
1 common fault alarm S.P.C.O or group 4  
4 user selectable S.P.C.O groups 5 to 8
RS232 data log – event log
Modbus – RS485 Audible alarm Alarm/Fault – permanent mute option Power 24v DC ±15% Control unit 7.5w quiescent 17w full alarm 

Sensor Cable
Main network – 4 core (2 power - 2 comms) 
1.5mm2 screened max length 1km 
Optional signal booster per additional 1km 


Miscellaneous
Remote reset/mute
Operating temperature: -10 to +50˚C

Dimensions
310W x 115H x 50D

Brochure Downloads

Click to View PDF Document

Combi 64 Panel Mount   

Version Changes

 
 
 

Combi Soft Download

Combi Soft

GDS Technologies CombiSoft is primarily data logging software to store readings from a Combi system

on an attached Windows based PC. Used for data acquisition, monitoring and configuration of the Combi 
addressable gas detection system, CombiSoft is a versatile tool for communicating with the GDS panel from
a computer. It allows the user to log unlimited data from all attached sensors on a single Combi system as 
well as control the system including calibration of sensors. 
The software is simple to install on a PC with Windows 7 and requires a single cable connection to the 
Combi panel (USB to serial).

Please ensure your PC is fully updated before the software is installed.

Click here :- download our .zip file, unzip the folder to your desktop or folder and run the .exe file to install *Please make a note of your Host ID number

For a full Combi Soft user licence, please contact our sales department quoting your Host ID number – sales@gds-technologies.co.uk