GDS Policy for Earth , zero volts and screen connections for sensor and panels

Summary

Gas system Installations generally have many differing methods of connection for Earth and screens and unfortunately some can cause problems with the operation of equipment through earth loops and signal noise. This document therefore states the preferred method of connection for land based and marine based GDS equipment .


Installation non hazardous
Screened multi core cables should be used in preference to non screened.
Power and signals can exist in the same multi core cable.
The sensor electronics is floating and not connected to the sensor enclosure.
Eg 3 core plus screen for use with powered 4-20mA sensors wired to a control panel.
core 1 is power from panel (usually 24v )
core 2 is zero volts from panel (0V)
core 3 is signal (source or sink to the control panel)
screen is wired to zero volts at the panel only.
(ie do not connect screen at the sensor head )
The sensor metal enclosure can be connected to local earth (ie mains earth) or left
floating. Do not connect to zero volts.

Installation flameproof
Armoured multi core cables with screen should be used in preference to non screened.
(note the Armour and the screen are separate conductors)
Power and signals can exist in the same multi core cable.
The sensor electronics is floating and not connected to the sensor enclosure.
Eg 3 core plus armour and screen for use with powered 4-20mA sensors wired to a control panel.
core 1 is power from panel (usually 24v )
core 2 is zero volts from panel (0V)
core 3 is signal (source or sink to the control panel)
screen is wired to zero volts at the panel only.
(ie do not connect screen at the sensor head )
Armour will be connected to the metal enclosure via the gland and can be
connected to local earth. or left floating . Do not connect to zero volts.

Multi drop Installations with data , flameproof
With networked sensors , a single cable is used with 2 or more sensors connected in parallel along the length of the cable.
Armoured multi core cables with screen should be used in preference to none screened.
(note the Armour and the screen are separate conductors)
Power and signals (usually data packets) can exist in the same multi core cable.
A Twisted pair should be used for the data signals.
The sensor electronics is floating and not connected to the sensor enclosure.
Eg 4 core plus armour and screen for use with powered intelligent sensors wired to a control panel.
core 1 is power from panel (usually 24v )
core 2 is zero volts from panel (0V)
core 3 is signal data + differential
core 4 is signal data - differential
screen is wired to zero volts at the panel only.
(ie do not connect screen at the sensor head except to make continuous through all sensors. See diagram 3.)
Armour will be connected to the metal enclosure via the gland and can be
connected to local earth. or left floating. Do not connect to zero volts.