Status 3-20 Way Alarm Panel

Product Overview

When any alarm input circuit receives a signal, the appropriate alarm LED will flash with the sounder and alarm relays turning ON. Pressing the reset switch will mute the sounder, and turn the red flashing alarm LED on constant, the relays will reset (option – non resettable relays). When the alarm signal has cleared pressing the reset switch will clear the alarm LED.

  • 20 Sensor Input Chanels
  • Visual and Audible Alarm
  • Wall Mountable

Additional Information

PDF Downloads

General Enquiries
Tel. +44 (0) 113 2860166

Email:
admin@gds-technologies.co.uk

Sales Enquiries:
Tel. +44 (0) 113 2878187

Email:
sales@gds-technologies.co.uk

Technical Engineering Advice
Tel. +44 (0) 113 2878184

Email:
admin@gds-technologies.co.uk

Status 3-20 Way Alarm Panel

System Funcltion:

When any alarm input circuit receives a signal, the appropriate alarm LED will flash with the sounder and alarm relays turning ON. Pressing the reset switch will mute the sounder, and turn the red flashing alarm LED on constant, the relays will reset (option – non resettable relays). When the alarm signal has cleared pressing the reset switch will clear the alarm LED.

System Test:
Pressing the reset pad for 15 seconds will turn all the alarm indicators on (stage 1), maintaining the reset pad on for a further 15 seconds will activate alarm relays and corresponding remote indicators (stage 2).

Power Supply 230/110V AC and/or 24V DC
Power consumption max 15 Watts
Indicators
Alarms (20 off) Red LED’s Conditions: Alarm mode – Flashing Accept mode – Constant
Fault Alarm Amber LED
Power Green/Red LED Conditions: Mains On – Green State Mains Fail – Red State (battery back-up mode)
System Test Stage 1 Alarm LED’s – ON Stage 2 Alarm relays – ON
Outputs Alarm Relays (1) 3 sets S.P.C.O.(Rating 5A 230vAC) Latched until alarm reset (option – not resettable until signal has cleared – factory setting) Fault Relay – Set S.P.C.O Rating 5A 230v AC Mains Fail Relay – Set S.P.C.O Rating 5A 230v AC
Audible Alarm Conditions: Gas / Fault Alarm (permanent mute option)
Signal Inputs – 20 way +24V DC (6 outputs) Field contacts, closing for alarm (20 inputs) Field contacts, closing for alarm Fault (1 input) Option at manufacture Alarm field contacts opening for +24V maintained alarm (loop failure monitored) connect jumper JP1-JP20 for unused inputs
Miscellaneous Enclosure Wall mount – steel enclosure IP52 314W 264H 55D Cable entry Base or rear Field terminals 2.5mm Remote reset 2 wire – N/O Remote sounder 2 wire – 24v DC
Options Channel Alarm Relays Add on board – 1 relay per channel

Top Accessories

For a full list of related products available please contact us via email sales@gds-technologies.co.uk