15/30J-win PID
Product Overview
The 15/30J-win PID is a safe area ABS flame retardant detector housing with display, designed to allow quick and easy access to its interior.
Features & Benefits
- Robust and weatherproof
- Flexible output options
- Addressable or stand alone
- Hyper Terminal communications RS232 line data and set up with 232 adapter
Additional Information
PDF Downloads
Safe Area Detector Head / Junction B ox Assembly Specification Sheet – ref C1506-B
Power Supply – 15 to 30vDC 24v nominal
Outputs – 3 wire – analog 4~20mA / 4 wire – CAN bus
Relays (optional) – Low alarm S .P.C.O 0.5A @30vDC / High alarm S .P.C.O / Fault alarm S.P.C.O / over-range
Inhibit option during servicing – Logging
Intervals – one minute to one hour
Storage – 2,880 readings
Temperature -15˚C to 55˚C
Humidity – 0˚C to 99% RH – non condensing
DETECTOR HEAD
Type – P1 Safe area use only
Ingress Protection – IP64
Material – ABS – Black
Sensor Type – Photoionisation – PID
Target Gases – VOC’s with ionisation potentials <10.6 eV See gas listing G645
Range – Isobutylene 0-200ppm (0-1000ppm max) / Isobutylene 5ppb to 50ppm options
Overrange – Isobutylene 5000ppm
Response Time – T90
Operating Life – Expected 5 years (excluding replaceable lamp and electronic stack – *6 months continuous operation)
Replacement Parts
010-644 PID Bulb*
010-645 PID Electrode Stack
010-646 PID Spring
010-647 PID Extraction Tool
JUNCTION BOX
Type – 30J Safe area use only
Ingress Protection – IP65
Material – ABS Flame retardent FR 40 / Lid Screws M4SS
Finish – Signal W hite RA L 9003
Weight – 380gms
Entries – Rear 5-20mm knock outs / Sides, Top, Bottom – not specified
Mounting – Standoffs – M4 or N o 8 screws / Drill at (C) when standoffs removed / Conduit box – drill at (A) 4.5mm / Surface mount box – drill at (B) 4.5mm
EU Design No. – 01359723-0001
Top Accessories
P1 Universal Fitting
P1 Watershield
P1 Collector Cone + Universal Fitting
P1 Flow Block